MDVH3016
Download Product Brochure
HV CT Operated Three Phase Meter
Type
MDVH3016
Accuracy Class
Active Class 0.2S
Reactive Class 2.0
Rated Voltage
3 x 230 / 400 V
Rated Current (Max)
3 x 1 (10) A
Frequency
50 Hz
Optical Test & Function Indicator
LED & Output Pulse
Meter constant for LED
10000 imp/kWh & 10000 imp/kVArh
Meter constant for Output Pulse
Configurable (5 I/O Port)
Typical Power Consumption
Voltage Circuit Active / Apparent Power at Un
< 2W / 10VA
Current circuit apparent power at Ib
< 1VA
Battery Life cycle
> 10 years
RTC Accuracy
< 5ppm
Class of Insulation
II
Degree of Protection
IP54
Auxiliary Supply Facility
(optional)
Isolation
4kV AC, 50 Hz, 1 min
High Voltage
Rise/fall time = 1.2/50μs and voltage = 10kV
Display LCD
8 digits, decimal places can be configured
Life cycle
10 years
Temperature Range Typical Operation
-25°C to +70°C
Temperature Range Storage
-40°C to +85°C
Dimension
Length x Width x Height = 302mm x 174.5mm x 80.5mm
Weight
Approximate 2.0 kg